Page:
|
1 of 4 FX291
|
Spec. No.
|
P5.1.1
|
Dated:
|
September 5, 2001
|
Issue:
|
1
|
Sarnia:
Technical:
|
1-800-265-7514
1-800-585-8857
|
|
1. |
GENERAL |
|
1.1 |
This standard sets forth specifications
and acceptable products for preformed pipe insulation of
0.5" to 24" inner diameters. (For inner diameters
greater than 24" see Equipment Insulation) |
|
1.2 |
This standard covers above and below grade
applications for piping systems operating at temperatures
ranging from ambient to 1200
ºF (649 ºC). |
| |
1.3 |
This standard will address wall thickness
and multiple layer recommendations. |
2. |
APPLICATIONS |
| |
2.1 |
HIGH TEMPERATURE PIPING 600 ºF(316
ºC) to 1200 ºF(649 ºC)
The pipe insulation shall be premolded and core formed.
A thermal
calculation should be performed to determine the proper insulation
thickness
to
ensure
either personnel
protection or process control. Where the insulation thickness
exceeds 3", a multiple layer system is recommended. |
| |
2.1.1 |
COMPOSITION:
Basalt wool and organic binder which is non-combustible and
asbestos free. |
| |
2.1.2 |
DENSITY:
The density to be between 6.8 and 8.6 pcf. |
| |
2.1.3 |
MAXIMUM THERMAL CONDUCTIVITY:
The thermal conductivity shall not exceed the following
as per ASTM C547
BTU in./ft2°F (W/m K)
|
Mean temperature
|
0.45 (0.065)
|
400°F (204°C)
|
0.54 (0.078)
|
500°F (260°C)
|
0.65 (0.094)
|
600°F (316°C)
|
0.77 (0.111)
|
700°F (371°C)
|
|
| |
2.1.4 |
MAXIMUM NON-FIBROUS (SHOT) CONTENT:
The percentage content of non-fibrous material (shot) shall
not exceed 20% by weight. |
| |
2.1.5 |
LINEAR SHRINKAGE:
The linear shrinkage, when tested at 1200°F (649°C), shall be
less than 1%. |
|
2.1.6 |
STRESS CORROSION:
The material must not promote or contribute to the corrosion
of austenitic stainless steel. |
| |
2.1.7 |
SURFACE BURNING CHARACTERISTICS:
as per CAN/ULC S102 AND UL E84
Shall not exceed
Flame Spread 5 Smoke Developed 0 |
APPROVED MANUFACTURE (S): FIBREX INSULATIONS,
INC.
Single or multiple layer - COREPLUS 1200 PIPE INSULATION
|